326
(c) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(d) Default value
A default value differs depending on modules to be used.
(15)CH
Control output cycle setting (address: 10CH, 13CH, 16CH, 19CH)
,
CH
Heating control output cycle setting (address: 10CH, 13CH, 16CH, 19CH)
, CH
Cooling control output cycle setting (address: 1C6H, 1CBH, 1D0H,
1D5H)
Set the pulse cycle (ON/OFF cycle) of the transistor output. In the heating-cooling control, the output cycle of the
heating control and cooling control can be set individually. 10CH, 13CH, 16CH, and 19CH are used for heating in
the heating-cooling control.
The ON time of the control output cycle is determined by multiplying the control output cycle by the manipulated
value (MV)
*1
(%) calculated by PID operation. If the manipulated value (MV)
*1
is constant, a pulse of the same
cycle is output repeatedly.
*1
For the heating control output cycle, the manipulated value for heating (MVh) is used. For the cooling control output
cycle, manipulated value for cooling (MVc) is used.
Ex.
When 700 (70%) is stored in CH
Manipulated value (MV) (RWr10 to RWr13) and 100 (100s) is set to
CH
Control output cycle setting (address: 10CH, 13CH, 16CH, 19CH)
The following calculation shows that the transistor output turns on for 70s and off for 30s per 100s.
• 100s
0.7 (70%) = 70s (ON time is 70s.)
Remote buffer memory
Default value
NZ2GF2B-60TCTT4
NZ2GF2B-60TCRT4
CH
Upper limit setting limiter (address: 10AH, 13AH, 16AH, 19AH)
1300
6000
CH
Lower limit setting limiter (address: 10BH, 13BH, 16BH, 19BH)
0
-2000
Standard
Heating-cooling
Heating-cooling
Control output cycle
ON
Manipulated value
(MV) (%)
OFF
Transistor output
ON
OFF
Control output cycle
100s
Manipulated value
(MV)(70%)
70s
Control output cycle
100s
Manipulated value
(MV)(70%)
70s
Control output cycle
100s
Manipulated value
(MV)(70%)
70s
Transistor
output
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......