Temperature Input Mode
When using this module as a temperature input module, use this mode.
(1) Setting method
1.
Set "Method selection" to "Param write (Station parameter)".
"CC IE Field Configuration" window
Select the temperature control module from "List of
stations"
[CC IE Field Configuration]
[Online]
[Parameter Processing of Slave Station]
2.
Set "100h:Temperature input mode" for "Control mode switching".
(2) Precautions
When resolution is "1", the temperature process value (PV) of the temperature control module is rounded off from
the actual temperature.
Ex.
When the actual temperature is 1299.5
, the temperature process value (PV) of the temperature control
module is 1300
.
To measure temperature by every 0.1
, set resolution to "0.1". (
Note that the temperature process value (PV) is not rounded off for the process alarm and rate alarm.
(
Page 140, Section 8.2.1 (1) (d), Page 141, Section 8.2.1 (2) (d))
Input from a temperature sensor
CC-Link IE Field Network
Master station
Temperature
control module