346
(43)CH
Process value (PV) scaling lower limit value (address: 201H, 204H, 207H,
20AH) ,
CH
Process value (PV) scaling upper limit value (address:
202H, 205H, 208H, 20BH)
Set the upper limit value/lower limit value of the temperature process value (PV) scaling function.
For details on the temperature process value (PV) scaling function, refer to the following.
(a) Setting range
The setting is -32000 to 32000.
(b) Enabling the setting
To enable the setting, turn off and on Initial data setting request flag (RY9) while the operations of all channels
are stopped.
(c) Default value
The default values are set to 0 in all channels.
The setting where the lower limit value is not less than the upper limit value does not cause an error. The temperature
process value (PV) is scaled according to the formula of
(44)CH
Alert 1 mode setting (address: 220H, 228H, 230H, 238H)
, CH
Alert 2 mode setting (address: 221H, 229H, 231H, 239H)
, CH
Alert
3 mode setting (address: 222H, 22AH, 232H, 23AH)
, CH
Alert 4
mode setting (address: 223H, 22BH, 233H, 23BH)
Set the alert mode of alert 1 to 4.
For details on the alert function, refer to the following.
(a) Alert mode and alert set value
Any alert set value can be set in each alert mode of alert 1 to 4 selected in this setting. Set the alert set value 1
to 4 in the following remote buffer memory areas. Alert set values 1 to 4 respectively correspond to alert modes
of alert 1 to 4.
Remote buffer memory area
name
Remote buffer memory address
Reference
CH1
CH2
CH3
CH4
CH
Alert set value 1
224H
22CH
234H
23CH
CH
Alert set value 2
225H
22DH
235H
23DH
CH
Alert set value 3
226H
22EH
236H
23EH
CH
Alert set value 4
227H
22FH
237H
23FH
Common
Common
Standard
Heating-cooling
Standard
Heating-cooling
Standard
Heating-cooling
Standard
Heating-cooling
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......