(2) Cyclic data update watch time setting (address: 7H)
This signal is used to set the time to watch the data update interval of the cyclic transmission (watch time).
When an update by cyclic transmission remains to be done for a set period of time for watching, the temperature
control module is regarded as disconnected. Then the module "continues its operation and produces external
outputs (HOLD)" or "stops its operation and external outputs (CLEAR)", according to HOLD/CLEAR setting
(address: 81H).
•
(a) Setting range
Setting range is Not monitor (0) or 1 to 20 (0.1 to 2 seconds). Set the value in increments of 100ms (1).
(b) Enabling the setting
To enable the setting, turn off and on Initial data setting request flag (RY9) while the operations of all channels
are stopped.
(c) Default value
The default value is set to Not monitor (0).
If a value out of the setting range is set, the error code (0930H) is stored in Latest error code (RWr0), Error flag (RXA) turns
on, and the ERR. LED turns on.
(3) Control mode shift (address: 80H)
Select the control mode. According to the setting, the control method for each channel changes as the following.
(a) Enabling the setting
To enable the setting, turn off and on Initial data setting request flag (RY9) while the operations of all channels
are stopped.
When the setting of Control mode shift (address: 80H) is changed, the remote buffer memory areas of address 100H and the
following addresses are overwritten to their default value.
Immediately after Control mode shift (address: 80H) is changed, an error (error code: 000DH) occurs. To eliminate the error,
turn on and off Set value backup instruction (RY15), and register a newly set parameter to the non-volatile memory.
Set value
Control mode
Number of control loops
Number of channels dedicated for
temperature Input
0H (default)
Standard control
Standard control 4 loops
1H
Heating-cooling control (normal
mode)
Heating-cooling control 2 loops
2
2H
Heating-cooling control (expanded
mode)
Heating-cooling control 4 loops
3H
Mix control (normal mode)
Heating-cooling control 1 loops
1
Standard control 2 loops
4H
Mix control (expanded mode)
Heating-cooling control 2 loops
Standard control 2 loops
100H
Temperature input mode
4
Common
Common
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......