(37)Cooling method setting (address: 1E6H)
Set the method for the cooling control in the heating-cooling control. Select the suitable cooling method for
cooling characteristics of devices.
The following figure shows the channel assignment of the remote buffer memory area.
For details on the cooling method setting function, refer to the following.
(a) Setting range
• 0H: Air cooled
• 1H: Water cooled
• 2H: Linear
(b) Enabling the setting
To enable the setting, turn off and on Initial data setting request flag (RY9) while the operations of all channels
are stopped.
(c) Default value
The default value is set to Air cooled (0H).
(38)During AT loop disconnection detection function enable/disable setting
(address: 1E7H)
Set whether to enable or disable the loop disconnection detection function during auto tuning (AT).
For details on the during AT loop disconnection detection function, refer to the following.
(a) Setting range
• 0: Disable
• 1: Enable
(b) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(c) Default value
The default values are set to Disable (0) in all channels.
Heating-cooling
b15
b0
b8
b7
b4
b3
b11
b12
CH4
CH3
CH2
CH1
to
to
to
to
Standard
b15
b3
b2
b1
b0
0
0
0
0
0
0
0
0
0
0
0
0
b4
CH4 CH3 CH2 CH1
Bit data from b4 to b15 are fixed to 0.
to
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......