APPENDICES
A
Appendix
4 EM
C
and Low Volt
ag
e
Direc
tives
Appendix
4.
1 M
e
asures
t
o
c
o
mply wit
h t
h
e
EM
C Direct
iv
e
(b) Immunity requirements
*1
The module is an open type device (a device designed to be housed in other equipment) and must be installed inside a
conductive control panel. The tests were conducted with the module installed in a control panel.
*2
The accuracy of an analog-digital converter module may temporarily vary within
10%.
(2) Installation in a control panel
The module is open type devices and must be installed inside a control panel.
This ensures safety as well as effective shielding of programmable controller-generated electromagnetic noise.
(a) Control panel
• Use a conductive control panel.
• When securing the top or bottom plate using bolts, cover the grounding part on the control panel so that
the part will not be painted.
• To ensure electrical contact between the inner plate and control panel, take measures such as covering
the bolts so that conductivity can be ensured in the largest possible area.
• Ground the control panel with a thick ground cable so that low impedance can be ensured even at high
frequencies.
• Holes in the control panel must be 10cm diameter or less. A hole with a diameter of 10cm or more may
cause leakage of radio waves. In addition, because radio waves leak through a clearance between the
control panel and its door, reduce the clearance as much as possible. The leakage of radio waves can be
suppressed by the direct application of an EMI gasket on the paint surface.
Our tests have been carried out on a control panel having the attenuation characteristics of 37dB (max.) and
30dB (mean) (measured by 3m method, 30 to 300MHz).
(b) Wiring of power cables and ground cables
• Near the power supply part, provide a ground point to the control panel. Ground the FG terminal with the
thickest and shortest possible ground cable (30cm or shorter).
Specifications
Test item
Test details
Standard value
EN61131-2: 2007
EN61000-4-2
Electrostatic discharge immunity
Immunity test in which
electrostatic is applied to the
cabinet of the equipment
• 8kV Air discharge
• 4kV Contact discharge
EN61000-4-3
Radiated, radio-frequency,
electromagnetic field immunity
Immunity test in which electric
fields are irradiated to the
product
80% AM modulation@1kHz
• 80M-1000MHz: 10V/m
• 1.4G-2.0GHz: 3V/m
• 2.0G-2.7GHz: 1V/m
EN61000-4-4
Electrical fast transient/burst
immunity
Immunity test in which burst
noise is applied to the power
supply line and signal line
• AC/DC main power, I/O power, AC I/O (unshielded): 2kV
• DC I/O, analog, communication: 1kV
EN61000-4-5
Surge immunity
Immunity test in which lightning
surge is applied to the power
supply line and signal line
• AC power line, AC I/O power, AC I/O (unshielded): 2kV
CM, 1kV DM
• DC power line, DC I/O power: 0.5kV CM, DM
• DC I/O, AC I/O (shielded), analog
, communication: 1kV
CM
EN61000-4-6
Immunity to conducted disturbances,
induced by radio-frequency fields
Immunity test in which high
frequency noise is applied to
the power line and signal line
0.15M-80MHz,
80% AM modulation @1kHz, 10Vrms
EN61000-4-8
Power-frequency magnetic field
immunity
Immunity test in which the
product is installed in inductive
magnetic field
50Hz/60Hz, 30A/m
EN61000-4-11
Voltage dips and interruption
immunity
Immunity test in which power
supply voltage is momentarily
interrupted
• 0%, 0.5 cycle, starts at zero crossing
• 0%, 250/300 cycle (50/60Hz)
• 40%, 10/12 cycle (50/60Hz)
• 70%, 25/30 cycle (50/60Hz)
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......