325
APPENDICES
A
Appendix
3 Det
a
ils of
Rem
o
te
Buf
fer Me
mory
A
reas
(13) CH
Setting change rate limiter unit time setting (address: 109H, 139H, 169H,
199H)
Set the time unit of setting change rate limiter.
For details on the setting change rate limiter time unit setting function, refer to the following.
(a) Setting range
• 0 (Not use time unit setting)
• 1 to 3600 (1 to 3600s)
When 0 is set, the operation is the same as the case when 60, a variation per minute, is set.
(b) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(c) Default value
The default values are set to 0 (Not use time unit setting) in all channels.
(14)CH
Upper limit setting limiter (address: 10AH, 13AH, 16AH, 19AH)
, CH
Lower limit setting limiter (address: 10BH, 13BH, 16BH,
19BH)
Upper/lower limit value of the set value (SV) can be set.
(a) Setting range
The setting range is identical to the temperature measurement range of the set input range. (
Appendix 3 (5))
The setting should meet the following conditions.
• CH
Lower limit setting limiter < CH
Upper limit setting limiter
If the above conditions are not met, a write data error (error code: 0005H) occurs.
(b) Setting unit
The value to be set differs depending on the stored value in CH
Decimal point position (address: 620H,
621H, 622H, 623H). (
• No decimal place (0): Set a value in 1
(
or digit) unit.
• One decimal place (1): Set a value in 0.1
(
) unit (tenfold value).
Standard
Heating-cooling
Standard
Heating-cooling
Standard
Heating-cooling
Input upper limit
Set value (SV) setting range
Input lower limit
CH□ Lower limit setting limiter
(address: 10BH, 13BH, 16BH, 19BH)
CH□ Upper limit setting limiter
(address: 10AH, 13AH, 16AH, 19AH)
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......