339
APPENDICES
A
Appendix
3 Det
a
ils of
Rem
o
te
Buf
fer Me
mory
A
reas
(30)CH
Overlap/dead band setting (address: 1C7H, 1CCH, 1D1H, 1D6H)
Configure the overlap/dead band setting.
For details on the overlap/dead band function, refer to the following.
(a) Setting range
Set the value within the following ranges for the full scale of the set input range. (
• -100 to -1 (-10.0% to -0.1%): Overlap
• 0 (0.0%): None
• 1 to 100 (0.1% to 10.0%): Dead band
(b) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(c) Default value
The default values are set to 0 (0.0%) in all channels.
(31)Alert dead band setting (address: 1E0H)
This setting is for using the alarm function.
For details on the alert function, refer to the following.
(a) Setting range
Set the value within the range 0 to 100 (0.0% to 10.0%) of the full scale of the set input range.
For details on the input range, refer to the following.
Ex.
When the value of the remote buffer memory is set as follows; CH
Input range (address: 100H, 130H,
160H, 190H): 2 (temperature measurement range: 0 to 1300
), Alert dead band setting (address:
1E0H): 5 (0.5%)
The following calculation shows that the dead band is the range of 6.5
with the alert set value being set
as the center of the range.
• (Full scale)
(Alert dead band) = (1300
- 0
)
0.005 = 6.5
(b) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(c) Default value
The default value is set to 5 (0.5%).
Heating-cooling
Standard
Heating-cooling
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......