219
CHAPTER 8 FUNCTIONS
8
8.
3 T
e
mperat
ure Cont
rol
M
ode
8.3.23
Overlap/dead band function
In heating-cooling control, the temperature process value (PV) significantly changes due to slight heating or cooling
control output when the heat produced by a controlled object and natural cooling are being balanced. Consequently,
excessive output may be performed.
The temperature where the cooling control output starts can be shifted using this function; therefore, whether control
stability is prioritized or energy saving is prioritized can be selected.
(1) Overlap
Overlap refers to the temperature area where both of heating control and cooling control are performed. In the
temperature area where both heating and cooling output overlap, both of the output negate each other, thus the
control gain becomes moderate. Consequently, the change amount in the temperature process value (PV) for the
output becomes small, improving control stability.
Ex.
When remote buffer memory values are set as follows:
• CH
Input range (address: 100H, 130H, 160H, 190H): 38 (temperature measurement range -200.0
to
400.0
)
• CH
Set value (SV) setting (address: 101H, 131H, 161H, 191H): 2000 (200.0
)
• CH
Overlap/dead band setting (address: 1C7H, 1CCH, 1D1H, 1D6H): -25 (-2.5%)
185.0
to 200.0
is the overlapping area.
(Full scale)
(Overlap setting) = (400.0
- (-200.0
))
-0.025 = -15.0
The temperature where cooling operation starts = (Set value (SV)) - 15.0
= 185.0
As shown below, shifting the temperature where cooling operation starts to the lower temperature side of the set
value (SV) produces an overlapping area. (The following is an example of when the module is in P control.)
Heating-cooling
100%
0%
-100%
Heating only
(manipulated value for cooling (MVc): 0%)
Heating/cooling
Cooling only
(manipulated value for heating (MVh): 0%)
Heating
Set value (SV) is 200.0°C.
Cooling
Temperature
process value (PV)
Temperature to start cooling
: 185.0°C
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......