36
(1) Type of usable temperature sensors, temperature measurement range,
resolution, and effect from wiring resistance of 1
This section describes the types of temperature sensors that can be used with the temperature control module,
the temperature measurement range, the resolution, and the effect from wiring resistance of 1
.
Set the temperature sensor to be used in the following remote buffer memory area.
• CH
Input range (address: 100H, 130H, 160H, 190H) (
(a) NZ2GF2B-60TCTT4
The following table lists the types of thermocouples that can be used with the NZ2GF2B-60TCTT4, the
temperature measurement range, the resolution, and the effect from wiring resistance of 1
.
*1
Means temperature error per 1
of wiring resistance of the thermocouple. The error varies depending on measured
temperature or ambient temperature. The temperature error can be corrected by the sensor correction function.
*2
While temperature can be measured within less than 400
/800
, the accuracy cannot be guaranteed.
Thermocouple
type
Temperature
measurement range
Resolution
Effect from wiring
resistance of 1
(
/
Temperature
measurement range
Resolution
Effect from wiring
resistance of 1
(
/
)
R
0 to 1700
1
0.030
0 to 3000
1
0.054
K
0 to 500
0 to 800
0 to 1300
1
0.005
0 to 1000
0 to 2400
1
0.008
-200.0 to 1300.0
-200.0 to 400.0
0.0 to 400.0
0.0 to 500.0
0.0 to 800.0
0.1
0.0 to 1000.0
0.1
J
0 to 500
0 to 800
0 to 1200
1
0.003
0 to 1000
0 to 1600
0 to 2100
1
0.006
-200.0 to 1000.0
0.0 to 400.0
0.0 to 500.0
0.0 to 800.0
0.1
0.0 to 1000.0
0.1
T
-200 to 400
-200 to 200
0 to 200
0 to 400
1
0.004
0 to 700
-300 to 400
1
0.008
-200.0 to 400.0
0.0 to 400.0
0.1
0.0 to 700.0
0.1
S
0 to 1700
1
0.030
0 to 3000
1
0.054
B
0 to 1800
1
0.038
0 to 3000
1
0.068
E
0 to 400
0 to 1000
1
0.003
0 to 1800
1
0.005
-200.0 to 1000.0
0.0 to 700.0
0.1
N
0 to 1300
1
0.006
0 to 2300
1
0.011
0.0 to 1000.0
0.1
U
0 to 400
-200 to 200
1
0.004
0 to 700
-300 to 400
1
0.009
0.0 to 600.0
0.1
L
0 to 400
0 to 900
1
0.003
0 to 800
0 to 1600
1
0.006
0.0 to 400.0
0.0 to 900.0
0.1
PLII
0 to 1200
1
0.005
0 to 2300
1
0.010
W5Re/W26Re
0 to 2300
1
0.017
0 to 3000
1
0.021
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......