296
(4) CH
Operation request flag (RY11 to RY14)
Turn on this signal to start operation for each channel.
• If the signal is turned on during the temperature control module stop, operation is started for the
corresponding channel and CH
Operation monitor (RX11 to RX14) turns on. Check that CH
Operation
monitor (RX11 to RX14) is on, and turn off the signal.
• If the signal is turned on during the module operation, the module keeps operating (CH
Operation monitor
(RX11 to RX14) remains on). An error or an alarm is not output.
• If the signal is turned on when an error has occurred, the module operation is not started. Eliminate the error
cause and turn on the signal again.
• If CH
Stop request flag (RY18 to RY1B) is turned on while the signal is on, an error occurs (error code:
001
H).
(5) Set value backup instruction (RY15)
Use this signal to write the remote buffer memory data to the non-volatile memory. Turning on the signal starts the
data writing to the non-volatile memory.
For the remote buffer memory areas whose data is to be backed up, refer to the following.
(a) When data writing to the non-volatile memory has been normally completed
Back-up of the set value completion flag (RX15) turns on.
(b) When data writing to the non-volatile memory has not been normally completed
Back-up of the set value fail flag (RX17) turns on. When Back-up of the set value fail flag (RX17) turns on, turn
on this signal to write the data to the non-volatile memory again.
(c) Timings when this signal cannot be accepted
In the following timings, this signal cannot be accepted.
• 1: While PID constants are being written automatically after auto tuning
• 2: While PID constants are being read from the non-volatile memory
• 3: When a setting error has occurred
• 4: While a setting is being changed with Initial data setting request flag (RY9)
• 5: While a setting is being changed with During operation setting change instruction (RY10)
For 1 to 3 above, turn on this signal again after each condition is resolved. For 4 and 5, the data writing to the
non-volatile memory automatically starts after the condition is resolved.
For details on the data writing to the non-volatile memory, refer to the following.
Common
OFF
OFF
OFF
ON
ON
CH□ Operation request flag
(RY11 to RY14)
Module status
CH□ Operation monitor
(RX11 to RX14)
Stop
Operation shift
processing
Operating
Controlled by the program
Controlled by the temperature control module
Common
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......