342
(36)Peak current suppression control group setting (address: 1E5H)
Set the target channels for the peak current suppression function and the gap of the control output cycle between
channels.
For details on the peak current suppression function, refer to the following.
(a) Setting range
• 0H: Not divide
• 1H: Group 1
• 2H: Group 2
• 3H: Group 3
• 4H: Group 4
(b) Enabling the setting
To enable the setting, turn off and on Initial data setting request flag (RY9) while the operations of all channels
are stopped.
(c) Default value
The default value is set to Not divide (0H).
The upper limit output limiter value is automatically set since the division number depends on this setting.
The following table lists the upper limit output limiter values which are set when this setting is enabled.
CH
Lower limit output limiter (address: 106H, 136H, 166H, 196H) is set to 0.
Division Number
CH
Upper limit output limiter (address: 105H, 135H, 165H, 195H) (
2
500 (50.0%)
3
333 (33.3%)
4
250 (25.0%)
Standard
b15
b0
b8
b7
b4
b3
b11
b12
CH4
CH3
CH2
CH1
to
to
to
to