Setting change rate limiter (address: 108H, 138H, 168H, 198H)
,
CH
Setting change rate limiter (temperature rise) (address: 108H, 138H,
168H, 198H)
, CH
Setting change rate limiter (temperature drop)
(address: 1C8H, 1CDH, 1D2H, 1D7H)
Set the change rate of the set value (SV) per a set time unit when the set value (SV) is changed. This setting can
regulate a rapid change of the manipulated value (MV). Set a time unit in CH
Setting change rate limiter unit
time setting (address: 109H, 139H, 169H, 199H). (
(a) Batch/individual setting of temperature rise and temperature drop
Setting change rate limiter for the temperature rise and the temperature drop can be set in a batch or
individually. Select the value on Setting change rate limiter setting (address: 1H. b1).
For details on the setting method, refer to the following.
When setting change rate limiter is set individually, 108H, 138H, 168H, 198H is for the temperature rise. The
following table lists the remote buffer memory areas to be referred to.
For details on the function, refer to the following.
(b) Setting range
The setting range is Disable (0), 0.1% to 100.0% (1 to 1000). Set the percentage of the full scale of the set
input range.)
• 0: Disable
• 1 to 10000 (0.1% to 100.0%. Set the percentage of the full scale of the set input range.)
(c) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(d) Default value
The default values are set to 0 in all channels.
Batch/Individual
Remote buffer memory area name
Remote buffer memory address
CH1
CH2
CH3
CH4
Batch
CH
Setting change rate limiter
108H
138H
168H
198H
Individual
CH
Setting change rate limiter (temperature rise)
108H
138H
168H
198H
CH
Setting change rate limiter (temperature drop)
1C8H
1CDH
1D2H
1D7H
Standard
Heating-cooling
Standard
Heating-cooling
Standard
Heating-cooling
Time
Temperature process value (PV)
Setting change rate limiter
(full scale percentage: 0 to 100%)
Set value (SV) 2
Set value (SV) 1
CH□ Setting change rate limiter unit time setting
(address: 109H, 139H, 169H, 199H)
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......