KATANA S610M Inverter Specialized for Elevator Manual
6.12 Performance Parameters (Group F11)
Function Code
Name
Setting Range
Factory Default
Value
F11.00
Carrier frequency
1.0
~
15.0kHz
Model confirmed
Table 6-6 Set carrier frequency of the inverter output PWM wave
Inverter Model
Factory default carrier frequency
Rated output current 71A and below
8.0 kHz
Rated output current 90A
7.0 kHz
Rated output current 176A and below
4.0 kHz
Attentions:
1.
Carrier frequency would affect noise intensity. Under normal circumstances, carrier frequency could be
set to 3
~
5kHz, while it should be set to 6
~
8kHz if quieter operation is required.
2.
When the inverter operates at the frequency which is above factory default carrier frequency, the inverter
needs derating use by 5% for each additional 1 kHz.
F11.01
Voltage regulation selection
000
~
FFFFH
0
LED units:
BIT0: over-debugging enable
0: Disenable
1: Enable
BIT1: Disposition method of over-debugging area
0: Method 0
1: Method 1
BIT2: Mode of wave-making
0: 7-segment mode
1: 7-segent cut over 5-segment mode
BIT3: Dead-zone compensation mode
0: Dead-zone compensation
1: none dead-zone compensation
LED tens:
BIT0: Narrow pulse control
0: don’t control
1: Control
BIT1: PWM selection
0: Normal PWM
1: Random PWM
BIT2: Over-voltage stalling selection (Reserved)
0: Prohibit (when the braking resister is installed)
1:Permit
BIT3: Selection of prohibit to decrease carrier wave
0: Permit to decrease carrier wave
1: Prohibit to decrease carrier wave
LED hundreds:
BIT0: Random sampling selection