Chapter 6 Function Codes in Detail
6.1 Basic Parameters (Group F00)
Function Code
Parameter Name
Setting Range
Factory Default
Value
F00.00
User’s password
00000
~
65535
00000
This function is to prohibit unauthorized personnel from reading and modifying any parameters.
This function is ineffective when F00.00=00000.
To make this function effective, first enter 5 digits as the user’s password and then press “ENTER” to
confirm. Without any further operations on buttons for 5 minutes, the password will be effective. After
entering the password, if no further button operations for more than 5 minutes, password protection would
be locked again.
Modification to the password: press “PRG” to enter into password verification state, enter the correct
password to enter into parameter editing state, choose F00.00 (F00.00
=
00000 displayed), enter new
password and press ENTER to confirm. If there are not any further operations on buttons for 5 minutes, the
new password becomes effective.
F00.01
Control mode selection
0
~
12H
11H
Units digit: mode selection of motor control
0: Open-loop vector control (without PG vector control)
i.e. speed-sensorless vector control, which can be applied for high-performance general variable-speed
driving.
1: Closed-loop vector control (with PG vector control)
i.e. speed sensor vector control, which is mainly applied for high-precision speed control, torque
control, simple servo control, and other strictly required high-performance control. Elevator control is also
in this mode.
2: V/F control
Controlled constant voltage/frequency ratio, which is especially applicable for multiple motors driven
by one inverter, to improve current speed regulation system.