70
KATANA S610M Inverter Specialized for Elevator Manual
Function Code
Name
Setting Range
Factory Default
Value
0: No slave machine
1~127: slave machine CAN node ID
F12.08
Detection time of CAN communication
overtime (under CAN mode)
0.1~10.0s
2.0
Available under CAN communication mode (F00.02=3 or 4). Detection time of CAN abnormal
communication.
F12.09
Detection time of CAN communication
overtime (under none-CAN mode)
0~10.0s
0
Available under none-CAN communication mode (F00.02<3). Detection time of CAN abnormal
communication. 0 doesn’t detect CAN communication error.
F12.10~F12.12
Reserved
0~3
0
6.14 System Management Parameters (Group F13)
Function Code
Name
Setting Range
Factory Default
Value
F13.00~F13.01
Reserved
0~4
0
F13.02
Parameters protection setting
0
~
2
0
0: Modification on all parameters permitted
1: except main digital frequency reference (F00.03) and this parameter (F13.02), modification on other
parameters prohibited
2: except this parameter (F13.02), modification on all other parameters prohibited
F13.03
Parameter initialization
0
~
2
0
0: parameter modification status
1: delete error records
2: reset to factory default setting
F13.04
Parameters copy
0
~
3
0
0: no action
1: upload parameters
2: download parameters
3: download parameters (except motor parameters)
Attentions:
Don’t upload/download the inverter parameters. After download parameters, CAN communication
distance control must re-learn the hoistway!
F13.05
Parameters display selection
0000
~
7FFFH
1C07H
Binary setting: 0
:
no display
;
1
:
displayed