KATANA S610M Inverter Specialized for Elevator Manual
Function Code
Parameter Name
Setting Range
Factory Default
Value
Figure 6-1 Torque boost (the boosted quantity shown as the shadow)
Attentions:
1. Improper setting of this parameter may cause the motor heating or over-current protection.
2. For definition of fz, please refer to F10.07.
3. 0.0% is automatical torque boost.
F00.09
One-key debugging of the elevator
menu
0
~
1
0
0: Normal menu
1: One-key debugging of the elevator menu
By this function, the operation panel displays the mode of one-key debugging, which means only the
commonly used parameters for on-site debugging will be shown to facilitate elevator debugging. In this
mode, when the last function code of current group is reached by flipping up/down, next group of function
codes will automatically show up. In other words, functions codes can be progressively increased/decreased
to the next group.
F00.10
Setting of elevator maintenance time
0
~
65535 hr
0
0: invalid
1: 0
~
65535 hours. This is to define the operating time before next round of maintenance for the
elevator, e.g. when F00.10 is set to 3000, the elevator needs maintenance after running for a time of 3000
hours (check F92.28 for operating time), and the inverter will report error E036. After maintenance, add
3000 more hours to this parameter, i.e.set F00.10=6000, then maintain the elevator after another 3000 hours
(check F92.28 for operating time). The inverter will report error E036.
6.2 Motor Parameters (Group F01)
Function Code
Name
Setting Range
Factory Default Value
F01.00
Rated power of the motor
0.4
~
90.0kW
Model confirmed
F01.01
Rated voltage of the motor
0
~
rated voltage of the inverter
Rated voltage of the
inverter
F01.02
Rated current of the motor
0.1
~
299.9A
Model confirmed
F01.03
Rated frequency of the motor
1.00
~
300.00Hz
Model confirmed
F01.04
Rated speed of the motor
0
~
60000RPM
1440