KATANA S610M Inverter Specialized for Elevator Manual
2.8 Installation Ambient
2.8.1 Requirements for the ambient
To ensure safe operations, please follow the below requirements for the installation ambient:
Please install the inverter in a clean ambient free from oil mist or dusts, or in an entirely closed cabinet
where floating substances cannot invade.
The system should be installed in an ambient without radioactive substances.
The system should be installed in an ambient free from corrosive gases or liquids.
The system should be installed in an ambient without direct sunlight.
The system should be installed in an ambient with less salt.
The ambient temperature should range from -10
℃
to 40
℃
. If exceeding 40
℃
, the inverter needs
external cooling or derating use.
The inverter should be installed in an ambient with vibration of less than 5.9m/s
2
(
0.6g
)
.
The ambient humidity is required to be lower than 90% without condensation.
The inverter should be vertically installed.
Altitude requirement: in regions exceeding 1000m, the cooling effect of the inverter becomes poor due
to thin air. Therefore, the output current shall be derated by 4‰ of the rated current for every 100m
increase.
Please consult and confirm with us if there’s any special requirements for installation.