36
KATANA S610M Inverter Specialized for Elevator Manual
Function Code
Parameter Name
Setting Range
Factory Default
Value
When the elevator running command and the actual direction are different, the actual direction can be
changed by modifying this parameter.
F00.06
Mechanical parameters of the motor
(display parameters)
10.0
~
6000.0
60.0
It reflects the correspondence between elevator speed and motor speed. This parameter are display
parameter.
F00.07
Maximum output frequency
5.00
~
100.00 Hz
50.00
The max. output frequency is the permitted highest output frequency.
Attentions:
It must be carefully set according to nameplate parameters of the motor in use and its actual
operating conditions.
F00.08
Motor torque boost
0.0%
~
30.0%
0
To compensate low-frequency torque, the output (OP) voltage can be boosted (valid under V/F
control). This function code is relative to max. output voltage, as shown in Figure 2-1.
In figure 6-1, variables are defined as follow:
f
b
:
basic operating frequency, i.e. the min. value of output frequency when the inverter is outputting
rated voltage of the motor. The factory default setting of S610M inverter is rated frequency of the motor.
V
max
:
Rated frequency of the motor, i.e. the corresponding output voltage when the inverter is
outputting basic operating frequency.
OP voltage
f
b
V
b
V
max
OPfrequency
f
z
V
b:
voltage of manual torque boost
V
max
: rated voltage
f
z
: cut-off frequency of torque boost
f
b
: basic running frequency