85
KATANA S610M Inverter Specialized for Elevator Manual
Function Code
Name
Setting Range
Factory Default
Value
F92.17~ F92.24
Resereved
F92.25
Temperature of radiator 1
0.0
~
150.0
℃
0.0
F92.26
Temperature of radiator 2
0.0
~
150.0
℃
0.0
Temperature of radiator 1 shows the temperature of inverter module. Over-temperature protection values of
the inverter module of different models might be different.
Temperature of radiator 2 shows the temperature of rectifier module. The rectifier bridge temperature is only
detected by models of 380V with power code 15 and above.
Displayed temperature range: 0
~
150
℃
; Precision: 5%.
F92.27
Accumulative power-on time
0
~
65535
小时
0
F92.28
Accumulative operating time
0
~
65535
小时
0
F92.29
Accumulative operating time of the fun
0
~
65535
小时
0
F92.27
~
F92.29 display accumulative power-on time, accumulative operating time of the inverter and the fan
since the inverter leaves the factory, respectively.
F92.30
ASR controller output
-300.0%
~
300.0%
0.0
This parameter is the ASR controller output as a percentage of rated torque of the motor.
F92.31
Higher bits of accumulative power
consumption
0~65535*10000kWh
0
F92.32
Lower bits of accumulative power
consumption
0~9999kWh
0
This parameter is for monitoring the output work.
F92.33
Operating efficiency of motor
0~100.0%
0
It is used to monitor the proportional relation between running time and pown-on time.
F92.34
Segment display of the inverter running
status
0
~
FFFFH (segment display)
0
The status of the nixie tubes in the operation panel shows current inverter status. In order to describe
clearly, we arranged the command of the nixie tubes in the operation panel in terms of the sequence of 5
,
4
,
3
,
2
,
1 from left to right. Every section of nixie tubes is defined as follows:
A
G
F
D
C
E
B
A
G
F
D
C
E
B
A
G
F
D
C
E
B
A
G
F
D
C
E
B
A
G
F
D
C
E
B
sequence
marker of