KATANA S610M Inverter Specialized for Elevator Manual
Function Code
Parameter Name
Setting Range
Factory Default
Value
The functions listed in above table will be explained as follows:
1: Forward 2: Reverse
These parameters are for operating control under control terminal mode. Please refer to table 6-2 as
shown below.
Table 6-2 Up/Down terminal description
Up Terminal
Down Terminal
Elevator State
OFF
OFF
Stop
OFF
ON
Going down
ON
OFF
Going up
ON
ON
Stop
3~5: Multi-speed terminals (MS1~MS3)
By arranging the ON/OFF combination of these terminals, we can define the operation curve of 8-section speed at most.
Table 2-3 Multi-speed operation selection list
multi-speed
terminal 3
terminal 2
multi-speed
terminal 1
multi-speed
setting
Function Code
OFF
OFF
OFF
Multi-speed0
F03.00
OFF
OFF
ON
Multi-speed1
F03.01
OFF
ON
OFF
Multi-speed2
F03.02
OFF
ON
ON
Multi-speed3
F03.03
ON
OFF
OFF
Multi-speed4
F03.04
ON
OFF
ON
Multi-speed5
F03.05
ON
ON
OFF
Multi-speed6
F03.06
ON
ON
ON
Multi-speed7
F03.07
6: External reset input
This terminal can reset the error when the inverter is in failure and warns about it. It has the same effect as that of the key
RESET on the operation panel.
7: External error input
Error signal from external devices can be input through this terminal to facilitate the error monitoring of them. When the
inverter receives error signals of external devices, it will display”E015” to warm about it.
8: Inspection input (INS)
When this terminal is effective, the elevator starts inspection operation and the upward & downward running of the elevator are
jointly controlled by the terminal and the keys UP (upward) & DN (downward).