KATANA S610M Inverter Specialized for Elevator Manual
Function
Code
Parameter Name
Setting Range
Factory Default
Value
recommended modifications on these parameters by users with cautions.
F06.15
Anti-vibration factor for the elevator
-1000
~
1000
0
When some mechanical reasons, such as large friction of guide shoes, over large/small elastic
coefficient of the steel wire rope, cause car shaking at normal speed, parameter F06.13
(
anti-vibration factor
of the elevator
)
can be adjusted to decrease the discomfort.
F06.16
Pre-torque selection
0~3
0
0: auto-torque compensation 1
1: auto-torque compensation 2
2: analog value reference of weighing-sensor (reserved)
3: pre-torque digital setting(reserved)
F06.17
Vibration depression mode selection of
torque automatical compensation 2.
0~3
0
0:
Vibration depression mode 1
1: Vibration depression mode 2
2: Vibration depression mode 3
3: Vibration depression mode 4
F06.18
Zero-speed torque limit selection
0~1
0
0: Utilize set torque to limit
1: Utilize default torque to limit
F06.19
~
F06.25
Reserved
F06.19
~
F06.25 are reserved functions.
F06.26
~
F06.35 Manufacturer debugging parameters
F06.26
~
F06.35 are manufacturer debugging parameters.
F06.36
Switch frequency of mode 1
0~100%
15%
This function code used to set switching frequency between IF control and VF control, which is the
percentage of motor rated frequency. If appear vibration nearby this frequency point during elevator
operation process, this parameter value could be increased a little.
F06.37
Low-frequency current given of mode 1
0~2000
1200
This function code is utilized to set max. given exciting current value when IF control (namely: exciting
current while zero-frequency operation). This value is based on the rated current of inverter, 1200 represents
120.0% of the rated current of inverter. Value of this function code could be adjusted appropriately in view of
slip inverse situation of elevator start. It will cause inverter over-load even over-current error if this value is
adjusted too large. This value should be adjusted smaller under the precondition of ensuring acceptable slip
inverse of elevator because too large value may cause shock during elevator starting or vibration during
elevator decelerate to creep.
F06.38~ F06.39 Manufacturer debugging parameters
F06.38~ F06.39 are manufacturer debugging parameters.
F06.40
Low-frequency current given of mode 1
0~2000
800