69
KATANA S610M Inverter Specialized for Elevator Manual
Function Code
Name
Setting Range
Factory Default
Value
F11.09
Fan control
0
~
1
0
0: Auto operation
The inverter will automatically start internal temperature inspection during operation, determining start
or stop of the fan based on the temperature of modules. If the fan is running before the inverter shutdowns,
the fan continues to run for 3 more minutes after the inverter shutdowns, and then the internal temperature
inspection will be started.
1: Fan keeps running when powered on
Fan keeps running after the inverter is powered on.
F11.10
Zero velocity threshold
0.001~0.010m/s
0.003m/s
Use this function code with the 10
th
function code of switch output terminal.
F11.11~F11.1
3
Manufacturer debugging parameter
F11.11~F11.13 are manufacturer debugging parameters.
6.13 Communication Parameters (Group F12)
Function Code
Name
Setting Range
Factory Default
Value
F12.00
~
F12.03
Reserved
0~4
0
F12.04
Type of CAN communication extension
card
0
~
1
0
0: CANlink
1: Reserved
F12.05
Baud rate of CAN communication
0
~
5
1
0
:
20 Kbps
1
:
50 Kbps
2
:
100 Kbps
3: 125 Kbps
4: 250 Kbps
5: 500 Kbps
F12.06
CAN local machine address
1
~
127
1
Local machine CAN node ID.
F12.07
CAN slave machine address
0
~
127
0