61
KATANA S610M Inverter Specialized for Elevator Manual
Function Code
Name
Setting Range
Factory Default
Value
F09.00
Relay output action selection when in
errors
000
~
111H
000
LED units digit: undervoltage error action selection, i.e. selection for whether the error indication is to act
when in undervoltage situation like powering on or powering off.
0: no action
1: action (undervoltage regarded as an error)
LED tens digit: action selection for auto reset interval error, i.e. selection for whether the error indication is
to act during auto-reset interval while the error has not been truly reported. Please refer to the description of
F09.05 and F09.06.
0: no action
1: action
LED hundreds digit: reserved
F09.01
Error screening selection 1
0000
~
2222H
0000
LED units digit: SCI communication error screening selection (Reserved)
LED tens digit: contactor error screening selection
LED hundreds digit: EEPROM error screening selection
LED thousands digit: reserved
0: not screeninged. Error reported and shutdown.
1: not screeninged. Error alert and continues operation.
2: screeninged
F09.02
Error screening selection 2
00
~
22H
00
LED units digit: input phase loss error screening selection
LED tens digit: output phase loss error screening selection
0: not screeninged. Error reported and shutdown.
1: not screeninged. Error alert and continues operation.
2: screeninged
Attentions:
Please be careful in choosing the error screening function. It must be correctly set after the error
cause is confirmed; otherwise wrong selection might cause expanded accidents, injuries or property
damages.
F09.03
Optimization mode selection
0~1111H
0
LED units digit:Prohibit to select the optimization protection of encoder wire-broken.
0: Start the optimization protection of encoder wire-broken.
1: Forbid the optimization protection of encoder wire-broken.