KATANA S610M Inverter Specialized for Elevator Manual
Termin
al No.
Terminal
screen
printing
Name
Function Description
Specification
X4
Multifunctional
Input X4
X5
Multifunctional
Input X5
X6
Multifunctional
Input X6
X7
Multifunctional
Input X7
X8
Multifunctional
Input X8
CN2
CANH
CAN
Communication
Standard CAN
communication interface.
Please use twisted-pair
wire or shielded wire.
CANL
Y1
Open collector
output Y1
These terminals are programmable
and can be defined as
multifunctional digital output
terminals. Please refer to functions
description of output terminals.
Opto-coupler isolation
open-collector output
Working voltage range:
9
~
30V
Max. output current:
100mA
Y2
Open collector
output Y2
COM
Y1/Y2 public port
R3A
Programmable
relay output 3
They can be programmed to be
defined as multifunctional relay
output terminals. Please refer to
functions description of output
terminals.
A-B: Normal Close (NC);
A-C: Normal Open (NO);
Contact capacity:
DC24V-1A
R3B
R3C
CN3
HV
Door lock AC110V
input
Input voltage range:
110±20%
HGND
R1A
Programmable
relay output 1
They can be programmed to be
defined as multifunctional relay
output terminals. Please refer to
functions description of output
terminals.
Contact capacity:
AC250V/DC24V-5A
The overvoltage grade of
input voltage of the relay
output terminal is grade II.
R1C
R2A
Programmable
relay output 2
R2C
CN4
Interface of
Handheld Keyboard
Apply to connect with Handheld
Keyboard
CN5
Interface of
Bluetooth
Apply to connect with Bluetooth
Module
Attentions:
1.
It is recommended using multicore shielded cable or twisted wire (above
1mm
2
) as the connecting wire
for control circuit terminals.
2.
When shielded cable is in use, the near end of the shielded layer (i.e. the end nearby the inverter)
should be connected with the grounding terminal PE of the inverter.
3.
The control cable should be wired more than 20cm away from main circuit and high-voltage circuit
(including power line, motor line, relay line, contactor line etc.). Vertical wiring is strongly
recommended instead of parallel wiring, so as to avoid false operation of the inverter due to
interference.