Table 2. DSA Preboot messages (continued)
v
Follow the suggested actions in the order in which they are listed in the Action column until the problem is solved.
v
See Chapter 4, “Parts listing,” on page 109 to determine which components are customer replaceable units (CRU) and
which components are field replaceable units (FRU).
v
If an action step is preceded by “(Trained service technician only),” that step must be performed only by a trained
service technician.
Message
number
Component
Test
State
Description
Action
201-805-xxx
Memory
Memory Test
Aborted
Test canceled:
the memory
controller
display/alter
write operation
was not
completed.
1. Turn off and restart the system.
2. Run the test again.
3. Make sure that the server firmware is at the
latest level. The installed firmware level is shown
in the diagnostic event log in the Firmware/VPD
section for this component. For more
information, see “Firmware updates” on page
213.
4. Run the test again.
5. If the failure remains, go to the IBM Web site for
more troubleshooting information at
http://www.ibm.com/systems/support/
supportsite.wss/docdisplay?brandind=5000008
&lndocid=SERV-CALL.
201-806-xxx
Memory
Memory Test
Aborted
Test canceled:
the memory
controller fast
scrub operation
was not
completed.
1. Turn off and restart the system.
2. Run the test again.
3. Make sure that the server firmware is at the
latest level. The installed firmware level is shown
in the diagnostic event log in the Firmware/VPD
section for this component. For more
information, see “Firmware updates” on page
213.
4. Run the test again.
5. If the failure remains, go to the IBM Web site for
more troubleshooting information at
http://www.ibm.com/systems/support/
supportsite.wss/docdisplay?brandind=5000008
&lndocid=SERV-CALL.
201-807-xxx
Memory
Memory Test
Aborted
Test canceled:
the memory
controller buffer
free request
failed.
1. Turn off and restart the system.
2. Run the test again.
3. Make sure that the server firmware is at the
latest level. The installed firmware level is shown
in the diagnostic event log in the Firmware/VPD
section for this component. For more
information, see “Firmware updates” on page
213.
4. Run the test again.
5. If the failure remains, go to the IBM Web site for
more troubleshooting information at
http://www.ibm.com/systems/support/
supportsite.wss/docdisplay?brandind=5000008
&lndocid=SERV-CALL.
64
System x iDataPlex dx360 M2: Problem Determination and Service Guide
Содержание System x iDataPlex dx360 M2
Страница 2: ......
Страница 16: ...xiv System x iDataPlex dx360 M2 Problem Determination and Service Guide...
Страница 138: ...122 System x iDataPlex dx360 M2 Problem Determination and Service Guide...
Страница 256: ...240 System x iDataPlex dx360 M2 Problem Determination and Service Guide...
Страница 262: ...246 System x iDataPlex dx360 M2 Problem Determination and Service Guide...
Страница 263: ......
Страница 264: ...Part Number 00D3199 Printed in USA 1P P N 00D3199...