EMC Test Item
Standard
ESD immunity
IEC 61000-4-2
Conducted susceptibility
EN/IEC 62040-2
EN/IEC 61000-4-6
Radiated susceptibility
EN/IEC 62040-2
EN/IEC 61000-4-3
Electrical fast transient
EN/IEC 62040-2
IEC 61000-4-4
Surge
EN/IEC 62040-2
IEC 61000-4-5
Impact current (lightning protection)
If a surge protection box is configured: 5 kA
(common mode), criterion B
Voltage dips and short interruptions (220 V AC) IEC 61000-4-11
Power frequency magnetic field
IEC 61000-4-8
11.4 Mains Input Electrical Specifications
Table 11-5 Mains input electrical specifications
Item
Specifications
Power system
Three-phase four-wire + PE/Three-phase three-wire + PE
Rated voltage
380 V AC/400 V AC/415 V AC (line voltage)
Voltage range
0–30°C: not derated at 323–485 V AC, derated from 100% load to
45% load at 323–191 V AC, and derated from 45% load to 35%
load at 191–138 V AC
30–40°C: not derated at 342–485 V AC, derated from 100% load to
45% load at 342–191 V AC, and derated from 45% load to 35%
load at 191–138 V AC
Rated frequency
50 Hz/60 Hz
Frequency range
40–70 Hz
Power factor
● > 0.99 (100% load)
● > 0.98 (50% load)
● > 0.94 (30% load)
UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
11 Technical Specifications
Issue 05 (2021-10-13)
Copyright © Huawei Technologies Co., Ltd.
375