Figure 6-416 Cable connection for an NC EPO port
Figure 6-417 Cable connection for an NO EPO port
NO TE
● When you use the NC status, remove the jumper between EPO_NC and EPO_12V first.
When you turn off the EPO switch, EPO is triggered.
● When you use the NO status, ensure that the jumper is connected between EPO_NC and
EPO_12V. When you turn on the EPO switch, EPO is triggered.
6.13 Verifying the Installation and Filling the Sealing
Putty
lists check items and acceptance criteria.
NO TICE
You need to carefully check items 08 and 09 listed in
. If the check
results of these two items do not meet the acceptance criteria, the UPS may be
damaged.
Table 6-17 Check items and acceptance criteria
No.
Item
Acceptance Criteria
01
Cabinet installation
The cabinets are securely installed and
do not tilt due to vibration.
UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
6 Installation
Issue 05 (2021-10-13)
Copyright © Huawei Technologies Co., Ltd.
322