Table 11-7 Battery electrical specifications
Item
Specifications
Battery voltage (lead-acid
battery)
360–600 V DC
● 12 V batteries (30–50 batteries optional, 0 by default)
– 40–50 batteries: not derated
– 38–39 batteries: derated to 90%
– 34–37 batteries: derated to 80%
– 30–33 batteries: derated to 70%
● 2 V batteries (180–300 batteries optional, 0 by default)
– 240–300 batteries: not derated
– 228–239 batteries: derated to 90%
– 204–227 batteries: derated to 80%
– 180–203 batteries: derated to 70%
NOTE
The number of batteries is 0 by default and needs to be set based on site
requirements. Batteries have no neutral wire, and an odd number of
batteries are supported.
Battery cold start
If a mains outage occurs, batteries can start the UPS to supply
power to loads.
Charger output power
Under rated conditions, the maximum charge power is 15% of
module power, and the charge current is limited to 30 A.
Battery string sharing
Lead-acid battery: Battery string sharing is supported in a parallel
system. No battery is shared by default.
SmartLi 2.0: Battery string sharing is supported. When multiple
UPSs are connected in parallel, the lithium battery cabinet can be
expanded for half a cabinet. No battery is shared by default.
SmartLi 3.0: not supported
Charging voltage (lead-acid
battery)
● Default equalized charging voltage: 2.35 V/cell
● Default float charging voltage: 2.25 V/cell
Battery type
● VRLA
● Adapts to SmartLi 2.0 and SmartLi 3.0 (SmartLi 3.0 supports
only the three-phase four-wire 380 V AC/400 V AC/415 V AC
voltage system).
11.7 Output Electrical Specifications
Table 11-8 Output electrical specifications
Item
1200 kVA
1600 kVA
Power system
Three-phase four-wire + PE/Three-phase three-wire + PE
UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)