NO TICE
The mains and bypass copper bars are heavy. To prevent personal injury or
device damage, arrange for two persons to work together.
Figure 6-249 Removing copper bars
Figure 6-250 Installing bypass input and output power cables
●
One power source
If the mains input and bypass input share a power source, you do not need to
remove the copper bar between the mains and bypass input terminals or
connect the bypass input power cable.
Step 13 Install battery cables.
UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
6 Installation