Indicator
Color
Status
Description
Blinking at
0.5 Hz
The communication between
the rectifier and the external
equipment is interrupted.
(When rectifiers are used in an
inductor cabinet, they do not
need to communicate with
external devices. It is normal
that the alarm indicator blinks
at 0.5 Hz.)
Fault indicator
Red
Off
The rectifier is normal.
Steady on
The rectifier locks out due to
output overvoltage.
The rectifier has no output due
to an internal fault.
Table 5-7 Specifications
Item
Specifications
Dimensions (H x
W x D)
40.8 mm x 95.5 mm x 208 mm
Weight
≤ 1.5 kg
UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
5 Optional Components
Issue 05 (2021-10-13)
Copyright © Huawei Technologies Co., Ltd.
79