Table 6-3 Recommended power cable cross-sectional areas (1300–1600 kVA)
Item
1300 kVA
1400 kVA
1500 kVA
1600 kVA
Mains input
Mains input
current (A)
2415
2601
2787
2972
Recomme
nded
cross-
sectional
area
(mm
2
)
L1
7 x 240
7 x 240
8 x 240
8 x 240
L2
7 x 240
7 x 240
8 x 240
8 x 240
L3
7 x 240
7 x 240
8 x 240
8 x 240
N
7 x 240
7 x 240
8 x 240
8 x 240
PE
2 x 240
2 x 240
2 x 240
2 x 240
Bypass input Bypass input
current (A)
1975
2127
2279
2431
Recomme
nded
cross-
sectional
area
(mm
2
)
L1
7 x 240
7 x 240
8 x 240
8 x 240
L2
7 x 240
7 x 240
8 x 240
8 x 240
L3
7 x 240
7 x 240
8 x 240
8 x 240
N
7 x 240
7 x 240
8 x 240
8 x 240
PE
2 x 240
2 x 240
2 x 240
2 x 240
Output
Output current (A) 1975
2127
2279
2431
Recomme
nded
cross-
sectional
area
(mm
2
)
U
7 x 240
7 x 240
8 x 240
8 x 240
V
7 x 240
7 x 240
8 x 240
8 x 240
W
7 x 240
7 x 240
8 x 240
8 x 240
N
7 x 240
7 x 240
8 x 240
8 x 240
PE
2 x 240
2 x 240
2 x 240
2 x 240
Battery
input (lead-
acid battery)
Nominal battery
discharge current
(A)
2881
3103
3324
3546
Maximum battery
discharge current
(A)
3451
3716
3981
4247
Recomme
nded
cross-
sectional
area
(mm
2
)
+
8 x 240
8 x 240
8 x 240
8 x 240
-
8 x 240
8 x 240
8 x 240
8 x 240
PE
2 x 240
2 x 240
2 x 240
2 x 240
UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
6 Installation
Issue 05 (2021-10-13)
Copyright © Huawei Technologies Co., Ltd.
100