NO TE
● After you set parameters on the Settings Wizard screen, choose System Info > Settings
> System Settings. Check that Requisite modules and Redundant modules match the
actual values.
● If dry contact signals are connected to the system, choose System Info > Settings > Dry
Contact Set. Check that the connected dry contacts have been enabled and that the
disconnected dry contacts have been disabled.
Step 3 If the system has connected to the remote EPO switch, you need to choose
Monitoring > UPS System > Running Parameter > System Settings on the
WebUI and set EPO detection to Enable.
Step 4 View the system running status diagram on the LCD to check that the UPS is
working in bypass mode.
----End
7.1.3 Starting the Inverter
UPS System User List
Table 7-1 UPS system user list
Default User
Preset Password
admin (administrator)
LCD
000001
Web
Changeme
operator (common user)
LCD
000001
Web
Changeme
Starting the Inverter on the LCD
Step 1 Choose Common Functions > Inv. ON.
NO TE
You can also start the inverter by choosing System Info > Maintenance > Inv. ON.
Step 2 On the displayed login screen, select a user name and enter the password.
Step 3 In the displayed dialog box, tap Yes to start the inverter.
----End
Starting the Inverter on the WebUI
Step 1 Open a browser (Internet Explorer 11 as an example) and choose Tools > Internet
Options.
Step 2 Click the Advanced tab, check that Use TLS 1.0 and Use TLS 1.1 are selected, and
click OK.
UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
7 Single UPS Commissioning
Issue 05 (2021-10-13)
Copyright © Huawei Technologies Co., Ltd.
330