11.2 Environmental Specifications
Table 11-2 Environmental specifications
Item
Specifications
Operating temperature
0–55°C
Temperature derating coefficient: not derated at 0°C–40°C, derated
to 0.9 at 41°C–45°C, derated to 0.8 at 46°C–50°C, and derated to
0.7 at 51°C–55°C
Storage temperature
–40°C to +70°C
Humidity
0%–95% RH (non-condensing)
Altitude
0–1000 m
When the altitude is greater than 1000 m, the power is derated as
described in IEC 62040-3. The upper limit of the altitude is 4000 m.
11.3 Safety Compliance and ECM Specifications
Table 11-3 Safety compliance
Safety Certification
Standard
CE
EN 62040-1:2013
CB
IEC 62040-1:2013
TUV
EN 62040-1:2013
CQC
CQC 3108-2011
CCC
GB 7260.1-2008
TLC
YD/T 2165-2017
RCM
IEC 62040-2
Table 11-4 EMC
EMC Test Item
Standard
Conducted emission
EN/IEC 62040-2
Radiated emission
EN/IEC 62040-2
Low-frequency signal interference
IEC 61000-2-2
UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
11 Technical Specifications
Issue 05 (2021-10-13)
Copyright © Huawei Technologies Co., Ltd.
374