Figure 6-400 Installing rectifiers and baffle plates
----End
6.6.4.3 Installing Cables
Procedure
Step 1 Install cables by referring to Single UPS Installation (1600 kVA, Three-Phase
Three-Wire) > Installation in Standard Configuration > Installing Cables.
Step 2 Remove an accessory cover from the top of the top air-flow cabinet.
Step 3 Connect the power cable to the 380~480V System port on the UPS, connect the
signal cable of the top air-flow cabinet on the leftmost to the PU XS2-1 in power
cabinet 1, and connect the signal cable of the other top air-flow cabinet to the PU
XS2-2 in power cabinet 2.
NO TE
The number and colors of cables in the figure are for reference only.
UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
6 Installation
Issue 05 (2021-10-13)
Copyright © Huawei Technologies Co., Ltd.
311