Table 7-2 DIP switch address mapping
No. 32
33
34
35
36
37
38
39
40
41
42
43
44
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
0
0
0
0
0
0
0
0
0
0
0
0
0
3
0
0
0
0
0
0
0
0
1
1
1
1
1
4
0
0
0
0
1
1
1
1
0
0
0
0
1
5
0
0
1
1
0
0
1
1
0
0
1
1
0
6
0
1
0
1
0
1
0
1
0
1
0
1
0
●
DIP switch settings on battery temperature sensors
When an ambient T/H sensor is used as a battery temperature sensor, set the DIP
switch to a value in the range of 16 to 28 to monitor the battery temperature.
Table 7-3 DIP switch address mapping (battery temperature sensor)
No
.
16 17 18 19
20
21
22
23
24
25
26
27
28
6
0
0
0
0
0
0
0
0
0
0
0
0
0
5
1
1
1
1
1
1
1
1
1
1
1
1
1
4
0
0
0
0
0
0
0
0
1
1
1
1
1
3
0
0
0
0
1
1
1
1
0
0
0
0
1
2
0
0
1
1
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
Step 2 Set UI parameters.
NO TICE
The address set on the software must be the same as the address set on the DIP
switch. Otherwise, the communication fails.
●
The DIP switch address of an ambient T/H sensor ranges from 32 to 44.
LCD: Choose System Info > Settings > Comm. Settings > Amb. T/H Sensor,
and set Start address and Quantity.
WebUI: Choose System Settings > Comm. Settings > Amb. T/H Sensor, and
set Start address and Quantity.
●
When an ambient T/H sensor is used as a battery temperature sensor, the DIP
switch address ranges from 16 to 28.
UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
7 Single UPS Commissioning
Issue 05 (2021-10-13)
Copyright © Huawei Technologies Co., Ltd.
350