Conductor material: 90°C flexible copper cable
–
It is recommended that AC power cables be no longer than 30 meters
and DC power cables be no longer than 50 meters.
NO TICE
When connecting power cables, comply with the tightening torque listed in
to ensure secure connections and prevent safety risks.
Table 6-4 Power cable terminal requirements
Port
Description
Connection Method
Bolt
Specifications
Bolt Length
Torque
Mains input
Crimped DT terminals
M12
45 mm
47 N·m
Bypass input
Crimped DT terminals
M12
45 mm
47 N·m
Battery input
Crimped DT terminals
M16
55 mm
120 N·m
Output
Crimped DT terminals
M12
45 mm
47 N·m
Equipotential
ground point
Crimped DT terminals
M6
20 mm
4.5 N·m
Table 6-5 Recommended input/output circuit breakers
Circuit
Breaker
Name
Specific
ations
a
(900
kVA)
Specific
ations
a
(1000
kVA)
Specific
ations
a
(1100
kVA)
Specific
ations
a
(1200
kVA)
Specific
ations
a
(1300
kVA)
Specific
ations
a
(1400
kVA)
Specific
ations
a
(1500
kVA)
Specific
ations
a
(1600
kVA)
Mains
input
circuit
breaker
2000
A/3P
2000
A/3P
2500
A/3P
2500
A/3P
3000
A/3P
3000
A/3P
3200
A/3P
3200
A/3P
Bypass
input
circuit
breaker
1600
A/3P
1600
A/3P
2000
A/3P
2000
A/3P
2500
A/3P
2500
A/3P
3000
A/3P
3000
A/3P
Output
circuit
breaker
1600
A/3P
1600
A/3P
2000
A/3P
2000
A/3P
2500
A/3P
2500
A/3P
3000
A/3P
3000
A/3P
a: recommended model when the short-circuit current where the circuit breaker is located is less
than 65 kA
UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
6 Installation
Issue 05 (2021-10-13)
Copyright © Huawei Technologies Co., Ltd.
102