Tools and Instruments
Lifting trolley
NO TE
lists only the common tools for installation and cable connection. For more dedicated
tools required, see the document for each component. Prepare tools based on site requirements.
6.1.3 Preparing Power Cables
NO TICE
● The UPS can generate large leakage currents. A circuit breaker equipped with a
residual current device (RCD) is not recommended.
● If the top cabling component and bottom cabling cabinet are not configured,
copper bars need to be prepared for the mains input, bypass input, and output,
which cannot be directly connected using cables.
If the top cabling component and bottom cabling cabinet are not configured,
prepare wiring copper bars for mains input, bypass input, and output based on the
following drawings and current requirements.
UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
6 Installation
Issue 05 (2021-10-13)
Copyright © Huawei Technologies Co., Ltd.