NO TICE
● A dry contact card port takes effect only after you set it in the software. You
need to disable unused dry contact signals.
● Set the EPO port to normally open (NO) or normally closed (NC) as required.
● If multiple UPSs are connected in parallel, connect all used dry contact signals
to each UPS.
● Signal cables must be double-insulated twisted cables. If the cable length is
within 25–50 m, the cross-sectional area must be 0.5–1.5 mm
2
.
● For dry contact outputs, the rated DC voltage and current are 24 V DC and 0.6
A and the maximum values are 30 V DC and 1.0 A. The rated AC voltage and
current are 24 V AC and 0.6 A and the maximum values are 30 V AC and 1.0 A.
During cable connection, ensure that the voltage and current do not exceed
these maximum values.
Figure 4-6 Appearance
Table 4-7 Functions of control signal ports on the dry contact card
Silk Screen
Signal Description
Status
Description
Initial
Status
BTG
Port for monitoring battery
grounding failures
● Closed: There is
a battery
grounding
failure.
● Open: There is
no battery
grounding
failure.
Open
a
0V
Port for signal ground
GEN
Port for detecting the diesel
generator (DG) mode
● Closed: DG
mode
● Open: non-DG
mode
Open
a
0V
Port for signal ground
BCB_OL
Port for monitoring the
battery circuit breaker (BCB)
box
● Grounded: BCB
box connected
● Disconnected:
BCB box not
connected
Grounde
d
UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
4 Component Description
Issue 05 (2021-10-13)