2. Install fan power cables by referring to Single UPS Installation (1600 kVA,
Three-Phase Four-Wire) > Installation in Top Air-Flow Configuration >
Installing Cables.
3. Install the top frame for the top air-flow cabinet (using the left side as an
example).
Figure 6-274 Installing the top frame
4. Install the mounting plates for the top air-flow cabinet (using the left side as
an example).
Figure 6-275 Installing mounting plates
6.6 Single UPS Installation (1600 kVA, Three-Phase
Three-Wire)
During installation and cable connection, do not step on the front door baffle
plate and the door support at the bottom of the cabinet to prevent paint flake-off
and deformation. Otherwise, the front door will not be properly closed. Do not
step on the top of the cabinet to prevent deformation or collapse.
6.6.1 Installation in Standard Configuration
UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
6 Installation
Issue 05 (2021-10-13)
Copyright © Huawei Technologies Co., Ltd.
242