Two power sources
Figure 6-368 Installing bypass input and output power cables
●
One power source
If the mains input and bypass input share a power source, you do not need to
remove the copper bar between the mains and bypass input terminals or
connect the bypass input power cable.
Step 14 Install battery cables.
NO TE
Battery cabinet connection requirements: If the UPS capacity is 800 kVA or lower, connect
battery cables only to the power cabinet on the left. If the UPS capacity exceeds 800 kVA,
connect battery cables equally to both power cabinets. If the number of battery cabinets is
an odd number, the remaining battery cabinet can be connected to any of the power
cabinets.
UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
6 Installation