Figure 5-17 Appearance
(1) Power indicator
(2) Alarm indicator
(3) Fault indicator
(4) Locking latch
(5) Handle
Table 5-6 Indicator description
Indicator
Color
Status
Description
Power indicator
Green
Steady on
The rectifier has an AC input.
Off
There is no AC input.
The rectifier is faulty.
Blinking at
0.5 Hz
Querying is in progress.
Blinking at
4 Hz
The rectifier is loading an
application program.
Alarm indicator
Yellow
Off
The rectifier has no protection
alarm.
Steady on
● The rectifier has generated
a warning due to ambient
overtemperature.
● The rectifier has generated
a shutdown alarm for
protection due to ambient
overtemperature or
undertemperature.
AC input overvoltage or
undervoltage protection has
been triggered.
The rectifier is hibernating.
UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
5 Optional Components
Issue 05 (2021-10-13)
Copyright © Huawei Technologies Co., Ltd.
78