Figure 6-112 Connecting a signal cable between the UPS and the SmartLi (only
for SmartLi 2.0)
(1) Monitoring interface unit in the master SmartLi cabinet
----End
6.4.2 Installation in Top Cabling Configuration
Cables can be routed from the top if the optional top cabling component is
configured.
6.4.2.1 Installing Cabinets
Installation on the Floor
NO TICE
Ensure that the installation floor is flat.
Step 1 Determine the cabinet installation positions on the floor based on the holes in the
marking-off template for floor installation.
NO TE
● A: mounting holes on the channel steel
● B: mounting holes on the floor
UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
6 Installation
Issue 05 (2021-10-13)
Copyright © Huawei Technologies Co., Ltd.
152