Step 12 Install signal cables.
●
If you need to log in to the WebUI of the UPS monitoring system, connect the
network port on a PC to the FE port on the monitoring interface card.
●
If the UPS needs to connect to an external network management device,
connect the external network management device to the RS485 port on the
monitoring interface card.
●
(Connection required only for SmartLi 2.0) If the UPS needs to connect to the
SmartLi, connect the COM port on the monitoring interface unit in the master
SmartLi cabinet to the COM2 port on the monitoring interface card.
NO TE
● Do not bind signal cables and power cables together.
● RS485 cables and FE cables must be shielded cables.
● The figure uses the cable connection between the UPS and the SmartLi as an example.
Figure 6-166 Connecting a signal cable between the UPS and the SmartLi (only
for SmartLi 2.0)
(1) Monitoring interface unit in the master SmartLi cabinet
Step 13 Install the UPS top frame.
UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
6 Installation
Issue 05 (2021-10-13)