NetCol5000-A020 Air Cooled In-row Precision Air
Conditioner
User Manual
3 Installation Guide
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
36
Figure 3-17
Holes on the bottom panel and top panel (unit: mm)
(1) Hole for routing drainpipes
(2) Hole for routing cables in the bottom
(3) Hole for routing cables in the bottom
(4) Hole for routing cables to the T/H
sensor
(5) Hole for routing the refrigerant liquid
pipes
(6) Hole for routing the refrigerant gas
pipes
(7) Hole for routing humidifier water supply
(8) Reserved hole
(9) Hole for routing cables in the top
(10) Hole for routing cables in the top
(11) Hole for routing cables to the T/H sensor
Inside diameter of the holes in the top and bottom with ring is 18.5 mm.
Do not make holes for routing cables in the bottom when routing cables from the top.
Do not make holes for routing cables to the T/H sensor (marked 4) in the bottom when routing
cables from the bottom but do not connect the T/H sensor outside the cabinet.
Step 7
Place and level the cabinet.