Alarm
ID
Alarm
Name
Alarm
Severity
Impact
Possible Causes
Solution
temperature.
3.
The ambient temperature
is lower than the lower
alarm threshold.
a004
Return-air 2
humid invalid
Major
The alarm
is
generated.
1.
The T/H sensor at return
air vent 2 fails to
communicate with the
main control board.
2.
Dirt or water exists
around the T/H sensor,
which leads to a
detection fault.
3.
The T/H sensor is faulty.
1.
Handle the Return air
2 humid invalid alarm.
2.
Clean the T/H sensor.
3.
Maintain or replace
the T/H sensor at
return air vent 2.
a007
Return-air 2
T/H brd
comm fail
Major
The alarm
is
generated.
1.
DIP switches of the T/H
sensor are incorrectly set.
2.
Cables to the T/H sensor
are loose or damaged.
3.
The T/H sensor is faulty.
1.
Set the DIP switches
of the T/H sensor by
referring to
C
Electrical Ports
.
2.
Check cables
connecting to the T/H
sensor.
3.
Maintain or replace
the T/H sensor.
a008
Comp HP
switch
Major
The alarm
is
generated,
and the
compressor
shuts down
forcibly.
1.
Cables to the high
pressure switch are loose
or damaged.
2.
The high pressure switch
is faulty.
3.
The solenoid valve is
faulty.
4.
Outdoor fans do not run
properly.
5.
The condenser is
blocked.
6.
The refrigerant is
overcharged.
1.
Check cables to the
high pressure switch.
2.
Maintain or replace
the high pressure
switch.
3.
Maintain or replace
the solenoid coil or
solenoid valve.
4.
Maintain or replace
the outdoor fans.
5.
Clean the condenser.
6.
Reclaim some
refrigerant.
a009
Comp HP
switch lock
Critical
The alarm
is
generated,
and the
compressor
is locked
and not
allowed to
be started.
The Comp HP switch alarm
is triggered for the
compressor multiple times
within a period.
Clear this alarm using the
solutions for alarm a008.
NOTE
After the alarm is cleared,
click
Manual clear
on the
alarm page.
a010
Comp suction
LP
Major
The alarm
is
generated,
and the
1.
Cables to the low
pressure switch are loose
or damaged.
2.
The low pressure switch
1.
Check cables to the
low pressure switch.
2.
Maintain or replace
the low pressure