5 System Operation and Maintenance
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
84
Alarm
ID
Alarm
Name
Alarm
Severity
Impact
Possible Causes
Solution
system
shuts down.
damaged.
3.
The smoke sensor is
faulty.
2.
Check cables to the
smoke sensor.
3.
Maintain or replace
the smoke sensor.
a045
Teamwork
mode failed
Major
The alarm
is
generated,
and a
message
"Networkin
g failed" is
displayed.
1.
Check that the group
control route is correct.
2.
The master and slave
NetCol5000-A020 units
have the same address.
3.
The master
NetCol5000-A020 is not
configured.
1.
Repair the group
control route.
2.
Change the
NetCol5000-A020
addresses.
3.
Configure the master
NetCol5000-A020.
a046
Comp freeze
point
protection
Critical
The alarm
is
generated,
and the
compressor
shuts down
forcibly.
1.
Cables to the
anti-freezing switch are
loose or damaged.
2.
The anti-freezing switch
is faulty.
3.
The solenoid valve is
faulty.
4.
The filter dryer is
blocked.
5.
The expansion valve is
blocked.
6.
The refrigerant leaks.
1.
Check cables to the
anti-freezing switch.
2.
Maintain or replace
the anti-freezing
switch.
3.
Maintain or replace
the solenoid coil or
solenoid valve.
4.
Maintain or replace
the filter dryer.
5.
Maintain or replace
the expansion valve.
6.
Check and rectify any
leakages. Charge
refrigerant after
maintenance or
replacement.
NOTE
After the alarm is cleared,
click
Manual clear
on the
alarm page.
a048
Supply-air
HT
Critical
The alarm
is
generated.
1.
The supply air high
temperature alarm
threshold is
inappropriate for the
working conditions.
2.
The temperature
displayed on the LCD is
different from the actual
temperature.
3.
The supply air
temperature sensor is
faulty.
4.
The refrigeration
capacity of the
NetCol5000-A020 is
insufficient or the heat
1.
Adjust the supply air
high temperature
alarm threshold.
2.
Calibrate or replace
the supply air
temperature sensor.
3.
Check cables to the
supply air temperature
sensor.
4.
Add more
NetCol5000-A020
units.
5.
Check the ambient
temperature.