4 Power-On Commissioning
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
69
Saturation
Temperatu
re (°C)
Pressure
(kPa)
Saturation
Temperatu
re (°C)
Pressure
(kPa)
Saturation
Temperatu
re (°C)
Pressure
(kPa)
10
988.4
35
2044.9
51
3041.7
11
1020.9
36
2098.9
52
3114.0
12
1054.1
37
2154.0
53
3187.7
13
1088.1
38
2210.2
54
3262.7
14
1122.9
39
2267.4
55
3339.1
15
1158.4
40
2325.6
N/A
N/A
Remove the steel refrigerant vessel after confirming that refrigerant no longer needs to be
supplemented.
User types include
Admin
(preset password: 000001),
Engineer
(preset password:
000001),
Operator
(preset password: 000001), and Guest users (no preset password).
The
Admin
user has the highest permission, followed by the
Engineer
,
Operator
, and
Guest
users. To enter
Diagnostic Mode
, you must have the
Admin
or
Engineer
rights.
If any alarm is reported during commissioning, handle the alarm by referring to
5.4 Alarm
Reference
and
5.5 Troubleshooting
.
If electric heater and electrode humidifier is not configured, skip the commissioning
procedures for the electric heater and humidifier.
Procedure
Step 1
Switch on the electric heater circuit breaker QF2, humidifier circuit breaker QF3, and
compromise distribution module circuit breaker QF4.
Step 2
Tap
Start
on the LCD, choose
Maint
>
Diagnostic mode
>
Enter
from the main menu.
For detailed operations, see
Advanced Cooling Controller User Manual
. After the equipment is powered
on, if no manual operation is performed within 25s, the equipment will automatically run following the
preset logic, and other components like the compressor and indoor and outdoor fans will also start as
required.
Step 3
Tap
On
of the outdoor fans in
Diagnostic mode
.
After that, check whether the OFF status of outdoor fans is cleared, the indicator of the phase
sequence protector inside the outdoor electrical control box is on. If the indicator is not on,
check whether the phase sequence works properly. For details, see
Advanced Cooling
Controller User Manual
.
Step 4
Tap
Off
of the outdoor fans in
Diagnostic mode
.
Step 5
Tap
On
of the liquid solenoid valve in
Diagnostic mode
.
You will hear a loud sound from the liquid solenoid valve after its status turns to
On
.