NetCol5000-A020 Air Cooled In-row Precision Air
Conditioner
User Manual
5 System Operation and Maintenance
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
92
Step 2
Check for any startup requirement for compressor on the LCD.
If no, the compressor does not need to start. It is not faulty, and troubleshooting is
complete.
If yes, go to
Step 3
.
Step 3
Check the compressor input power supply.
Unplug the X115 compressor terminal, measuring the terminal voltage of the docking surface.
If the voltage tolerance between 1 and 2, 2 and 3, 1 and 3 is ±10%, judged the power supply is
normal.
Figure 4-3
shows the X115 terminal position.
If the power input is normal, the compressor is faulty. Replace it by referring to
5.6.3
Replacing the Compressor
, and check whether the fault is rectified.
−
If yes, troubleshooting is complete.
−
If no, go to
Step 5
.
If the power input is faulty, go to
Step 4
.
Step 4
Check the compressor power supply.
If the power supply is faulty, check whether the compressor cable is normal and the
compressor circuit breaker is switched on. If there is problem, check whether the fault is
cleared after solution.
−
If yes, troubleshooting is complete.
−
If no, go to
Step 5
.
If the power supply is normal, go to
Step 5
.
Step 5
Contact Huawei technical support.
----End
5.5.3 Compressor Generates Excessive Noises
Symptom
Compressor generates excessive noises.
Possible Causes
The transport sheet metal is not removed from a compressor.
The compressor starts and stops continuously.
The compressor exists liquid strike.
Procedure
Step 1
Check whether the transport sheet metal is removed.
If no, remove the sheet metal and then check whether the fault is rectified.
−
If yes, troubleshooting is complete.
−
If no, go to
Step 2
.
If yes, go to
Step 2
.