NetCol5000-A020 Air Cooled In-row Precision Air
Conditioner
User Manual
3 Installation Guide
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
49
Figure 3-30
Zoomed-in view of the control terminal X106 port
Table 3-10
describes the definitions and functions of control ports.
Table 3-10
Definitions and functions of control ports
Terminal Definition
Function
Dry Contact
Feature
01, 02
Port for reporting
common alarm 1
Reserved
Reserved
03, 04
Port for reporting
common alarm 2
Reserved
Reserved
05, 06
Port for the
startup and
shutdown of an
outdoor unit
The signal output cables for
controlling startup and
shutdown of an outdoor unit are
connected to terminals 05 and
06. (One indoor unit
corresponds to one outdoor unit.
Terminals 05 and 06 are
connected to ports 1B/2B and
1A/2A of the outdoor unit
respectively.)
N/A
07, 08
Port for the
remote shutdown
of an indoor unit
Terminals 07 and 08 can be set
to remotely shut down an indoor
unit. Specifically, the control
signal cable is routed from the
ports to the monitoring room
Can connect to the
dry contact input, but
cannot connect to
active loads. The dry
contact must be used